SDB-2-2450-A

Clean Power Variable Frequency Drive, input 3x 600V, rated output 70A, IP20, embedded AFE

Main features

  • Variable frequency drive for AC motors
  • Pure sine wave 3-phase power output
  • Clean Voltage sine wave, V/f open and close loop
  • Field Oriented Control open and close loop
  • Multifunctional, digital and analog IOs
  • Built-in safe torque off (STO) inputs
  • SIL 3 capacity level to IEC61800-5-2
  • 24 VDC power supply input
  • Dual Ethernet port
  • Fire emergency mode
  • Configurable Linear and S-curve ramps
  • Starting torque boost
  • Integrated EMC filters
  • Set, monitor, control it with an app
  • Pluggable display
  • Natural language user interface

Description

The SmartD Clean Power Variable Frequency Drive is a compact AC drive utilizing SmartD’s patented own algorithms combined with WBG transistor technology. Producing a clean and pure sine wave to power and control 3-phase AC induction motors has never been easier. The SmartD VFD has essential features built-in for space, wiring and time savings, it eliminates the need for filters on the output, and guarantees longer motor lifetime.

This post is also available in: Français

SDB-2-2450-A specs

Product function Variable frequency drive for AC motors
Controlled motors Asynchronous 3-phases motors
Synchronous  3-phases motors (Permanent magnet)
Control Methods Clean Voltage sine wave, V/f open and close loop.
indirect Field Oriented Control (iFOC) open and close loop
Input Power Voltage 3 x 600 VAC  -15% / +10%
Input Power Frequency 50 and 60Hz +/- 5%
Input line current rms at 50 °C (122 °F) Rated input current 74A
Apparent power 45 kVA  @600V
Prospective Line Isc 100  kA
THDi <5 % from 80…100 % of load conforming to IEC 61000-3-12
Output Current rms at 50 °C (122 °F) Normal operation (continuously available without overload) 70A
Heavy duty operation 50A
Motor Power kW normal duty (1) 3x400VAC 50/60Hz
Motor Power kW heavy duty (1)
Motor Power HP normal duty (1)
Motor Power HP heavy duty (1)
Motor Power kW normal duty (1) 3x460VAC 50/60Hz
Motor Power kW heavy duty (1)
Motor Power HP normal duty (1)
Motor Power HP heavy duty (1)
Motor Power kW normal duty (1) 3x560VAC 50/60Hz max 45 KW
Motor Power kW heavy duty (1) max 37.5 KW
Motor Power HP normal duty (1) 60 HP
Motor Power HP heavy duty (1) 50 HP
(1) motor power values are indicative. They vary with the motor type, technology and manufacturer.
The variable frequency drive must not be selected from motor power rating
The variable frequency drive must be selected by skilled and experienced personnal.
The variable frequency drive must be selecting according to motor FLA, the load’s driving force and the movement cycle, and the operating environment.
Maximum Transient Output current Normal operation 110% of Normal Duty rated current during 60s every 10 min at 50 °C (122 °F)
Heavy duty operation 150% of Heavy Duty rated current during 60s every 10 min at 50 °C (122 °F)
Permissible temporary current boost
(motor starting)
Normal operation ≥ 140 A at 50 °C (122 °F) during 2s
Heavy duty operation ≥ 140 A at 50 °C (122 °F) during 2s
Short-circuit current for immediat tripping ≥ 210 A at 50 °C (122 °F
Output Frequency range of the drive 0.001 to 0.5 kHz
Speed drive output Frequency 0.1 to 120 Hz
Nominal switching frequency 105 kHz
effective switching frequency 210 kHz
efficiency 8 points graph as per IEC61800-9 ≥ 97%
IE Class 2
Deratings Ambient temperarure derating -15…50 °C without derating
>50…60 °C , Derate 2% for every 1 °C (1.8 °F)
Altitude derating no derating up to 2000 m
Braking Regenerative braking through AFE
Voltage 24 VDC
Limits 20.4 VDC to 28.8 VDC
Built in protection of auxiliary power input Reverse polarity and overvoltage
Standard to comply with IEC 61131-2 type 1
Digital input numbers 6
Digital inputs common terminal 1
inputs 1 and 2 Settable by user usable for encoder
inputs 3 to 6 Settable by user settable by user
input logic wire-able as sink or source, configurable by software
default: source
Source mode logic thresholds ON: 18 .. 24V / OFF: 0 .. 6V
Sink mode logic thresholds ON: 0 .. 6 V / OFF: 18 .. 24 V
Current consumption 6mA
Auxiliary Output power for digital inputs +24VDC (20% .. +20%) / 100 mA
Built in protection of Auxiliary output power overcurrent and overvoltage
STO (safe torque off) inputs Number of STO inputs 2
SIL capacity SIL 3 capacity level – conformed to IEC61800-5-2
stop category category 0
STO input reaction time < 20 ms
STO input filtering time 3 ms
Nominal voltage of STO enabling input 24V
Maximum input voltage 28.8V
Logic threshold 10V (+/- 5V)
Low state maximum voltage
for disable to SIL3 and Ple
5V
Digital output numbers 3
relay 1 relay output SPDT (form C) NO Contact Resistive load, AC: 5 A @ 250 V / DC 5 A @ 30 V
NC Contact Resistive load, AC: 3 A @ 250 V / DC 3 A @ 30 V
relay 2 and 3 relays output NO (form A) Resistive load, AC: 3 A @ 250 V / DC 3 A @ 30 V
Analog input numbers 3
Analog input types settable by users 0..10VDC
0..20mA / 4..20mA
0..24VDC
Impedance to read PTC temperature sensor
Input impedance 0..10VDC: input impedance > 3.5 k Ohms
0..20mA / 4..20mA: input impedance 165 Ohms
0..24VDC: input impedance > 3.5 k Ohms
Resolution 12 bits
Sampling time 2ms
Accuracy ± 1% at 25 °C (77 °F) / ± 2% for a temperature variation of 60 °C (108 °F)
Reference power supply for potentiometer +10 VDC / tolerance ± 2% for the temperature range of 20 °C to 30 °C / Current : maximum 10 mA, short circuit protected
Analog ouput numbers 2
Analog output types settable by users 0..10VDC ( ≥ 15 mA)
0..20mA / 4..20mA
Analog output impedeances 0..10VDC: output impedance 500 Ohms minimum
0..20mA / 4..20mA: output impedance 500 Ohms maximum
Resolution 12 bits
Sampling time 2ms
Accuracy ± 1% at 25 °C (77 °F) / ± 2% for a temperature variation of 60 °C (108 °F)
Analog outputs built-in protection overvoltage and overcurrent
Embedded ports on 2 RJ45 Modbus TCP
Wireless for Settings BLE
Width 12 in (30.48 cm)
Height 28 in (71.12 cm)
Depth 10 in (25.4 cm)
Net weight
Relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
Ambient air temperature for operation -15…50 °C without derating 50…60 °C with derating factor 2% for every 1 °C (1.8 °F)”
Ambient air temperature for storage -40…70 °C
Cooling Integrated, replaceable fans
Operating altitude <=2000 m without derating
Environmental characteristic Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3
Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
Ingress Protection IP IP20
Protection Degree UL (nema) type 1
Functionnal safety UL/IEC 61800-5-1 :2007+AMD:2016CSV
EMC IEC 61800-3 : 2017 emissions ; IEC 61000-4 immunity; IEC 61000-4-11 -34 voltage variations
Harmonics IEC 61000-3-12 ; IEEE 519
Generique IEC 61800-2 : 2021
EcoDesign / Energy efficiency IEC 61800-9
Safety standard ( STO) IEC 61508 part 1 and part2 ; IEC 62061 :2021
Cybersecurity IEC 62443
Environmental IEC 60068-2 ; WEEE directive ; RoHS
CERTIFICATIONS UL: pending

* Specifications are subject to change without notice.

Benefits

sine wave

Ultra-low harmonics

Clean Power VFD offers ultra-low harmonics, reducing electrical noise and increasing energy efficiency for your equipment.

filterless

Filter-less

Clean Power VFD is filter-less, providing cost-effective and maintenance-free operation for your equipment.

Symbol of IGBT

Active Front End (AFE)

Clean Power VFD features an active front end, enabling power factor near unity, ultra-low harmonics and regenerative braking for improved energy efficiency.

Smaller VFD

Space divided by 2

Clean Power VFD being of compact design, and eliminating the need for filters, saves up to 50% of space and simplifies equipment wiring.

Sine Wave

Clean signal

Clean Power VFD using the last technology of electronic power components, patented algorithm and embedded filters, it produces a clean sine wave.

SmartD motor control

Extended motor lifetime

Clean Power VFD’s advanced performances reduce motor insulation stress, bearing damage, and electrical noise for a longer motor lifetime.

// the pursuit of clean power

Our Journey to the Clean Power VFD

Tap the image to see the story

INCEPTION:
Simon Leblond and Simon Caron create SmartD Technologies Inc, in 2018, Montreal Quebec.

INNOVATION:
SmartD builds the first Wide-bandgap-based VFD technology on the market - offering Clean Power in a way that has not been done before. To achieve this level of technology, SmartD work with some of the most advanced WBG specialists in the industry.

Clean Power VFDs

IMPACT:
Partnerships are established with SE Ventures, the Power Electronics and Industrial Control Research Group (GRÉPCI), PME MTL, and the Canada Research Chair in Electrical Energy Conversion and Power Electronics.

SmartD Investors
// EASY SELECTION

VFD Selection Made Easy

Simpler from A to Z

Easiness starts with the selection of the right product. The offer structure of SmartD’s Clean Power VFD is built to ease the decision and avoid complex choices between multilevel of options

Easiness starts with the selection of the right product. The offer structure of SmartD’s Clean Power VFD is built to ease the decision and avoid complex choices between multilevel of options

VFD decoder: understand your drive model

Book A Demo Right Now!

SmartD Clean Power is real and it is ready to revolutionize motor control. Don’t just take our word for it, see it for yourself. 

// FAQ

Frequently Asked Questions

What is a Variable Frequency Drive?

A variable frequency drive (VFD) is an electronic device that controls electric motor speed by varying the frequency and voltage supplied to the motor.

A VFD adjusts the motor’s speed to match the load requirement, this helps to drastically reduce energy consumption.

Other names for a VFD are variable speed drive, adjustable speed drive, adjustable frequency drive, AC drive, and inverter.

Why is the Clean Power VFD the right choice?

SmartD’s Clean Power variable frequency drive generates pure-sine electrical signals in a package half the size that is twice as efficient.

Forget messy cables and bulky filters. Experience Clean Power in a compact footprint.

How much time does the SmartD Clean Power VFD take to set up?

3 cables in, 3 cables out. That's it. Set it up and let it do its thing in under 30 minutes.

Will the SmartD Clean Power VFD work with our existing systems?

Our products are IoT, BMS and SCADA ready.
Ethernet and Modbus connectivity for integration to Cloud, BMS and SCADA systems.

Is the SmartD Clean Power VFD available for purchase?

The SmartD Clean Power VFD will be available for purchase Q3, 2022.

SmartD Clean Power VFD